Up to 15 User defined linearization points available. The user linearization feature allows the volume of a tank’s contents to be calculated from the height of the material in that container. Up to 15 linearization points can be defined by user in the measurement range
The IST-P DIN rail transmitter is user configurable with Thesoftware and interface cable URC-1020. Theis user-friendly software. The latest release version can be download free from website. Interface cable consist of interface converter and USB plug. It can be purchased separately from Thesupplier. During configuration the transmitter can work alone without connecting to a power source.
Specification
Input
200Ω~60K Ω
Accuracy
± 0.1% F.S.
A/D Resolution
16 bits
Input Sampling Rate
<200 ms
Power Supply
DC 10 to 36V
Max. Load
Max Load =(V-10)/ 0.02(Ω)
Output Resolution
0.6 μ A(15 bits)
Output Response Time
<200 ms
Common Mode Rejection Ratio
(CMRR)
>80 dB
Compatibility
En 50081-2, En 50082-2
Galvanic Isolation
3.75 KV. between input and output
Operating Temperature
-10 to 50°C
Humidity
0 to 90% RH
Loop Power Signal Transmitter
Model
Type
Input
Output
Isolated
T/C
PT100
mV
mA
V
IST-H
Head Mount
V
V
V
X
X
4-20mA
V
IST-D
DIN Rail
V
V
V
V
V
4-20mA
V
IST-P
Head Mount
0-60KΩ
4-20mA
V
NST
Head Mount
V
V
V
X
X
4-20mA
X
Dual Channel Isolated Signal Converter
Model
Type
Input
Output 1
Output 2
Math Function
Independent
Input(*Note)
T/C
PT100
mV
mA
V
ISC-D
DIN Rail
V
V
V
V
V
0-24mA/0-10V
0-24mA/0-10V
V
X
ISC-C
DIN Rail
V
V
V
V
V
0-24mA/0-10V
RS485
V
X
ISD-D
DIN Rail
V
V
V
V
V
0-24mA/0-10V
0-24mA/0-10V
X
V
ISD-C
DIN Rail
V
V
V
V
V
0-24mA/0-10V
RS485
X
V
ISA-D
DIN Rail
X
X
V
V
V
0-24mA/0-10V
0-24mA/0-10V
X
V
ISA-C
DIN Rail
X
X
V
V
V
0-24mA/0-10V
RS485
X
V
*Note:
ISD/ISA: Different input type can be set to each channel
ISC: Both channels must be set to same input type