PRODUTCTS  
     
 

 

   
Home > Products > Controllers & Indicators > SD 430 Microprocessor Indicator  
 
  SD 430 Microprocessor Indicator  
 

 

 

Catalog

Manual

RS-485

Software
  • 4"Large LED Display. 
  • T/C, RTD, mV, mA, V, and Digital Input selection. 
  • Universal power supply : 90~264VAC, 50/60Hz.
  • 2 Alarm output. (Note 1) 
  • Standby and Latch mode can be combined with 8 different alarm
    functions. 
  • 4~20mA or 0~10Vdc retransmission and RS-485 communication
    (MODBUS RTU) are available for option.
  • USB configuration port. 
  • Note1: 1st and 2nd Alarm are available for option.
 
Specifications
Input Thermocouple : J. K. T. E. B. R. S. N.C
RTD : DIN PT-100; JIS PT-100
Linear : 4~20mA; 0~50mV; 1~5V; 0~10V…
Accuracy T/C±1°C; RTD±0.2°C; Linear±3μV
Sampling Time 0.25 sec. (8 sample/sec) 125 ms
Alarm Relay Contact Output : 10A / 240 VAC (Resistive load)

Retransmission

Current Output : 4~20mA; (Resistive 600 Ωmax.)
Continuous Voltage Output : 0~50mV; 1~5V; 0~10V..... 
(Resistive 600 Ωmin.)
General Rated Voltage : AC 90~264VAC 50 / 60HZ
Ambient Temperature : 0~50°C
Ambient Humidity : 0~90%
Consumption : Less than 3VA
 
Input
Type Temperature Range
J -50 ~ 1000°C -58°F ~ 1832°F
K -50°C ~ 1370°C -58°F ~ 2498°F
T -270°C ~ 400°C -454°F ~ 752°F
E -50°C ~ 750°C -58°F ~ 1382°F
B 0°C ~ 1800°C 32°F ~ 3272°F
R 0°C ~ 1750°C 32°F ~ 3182°F
S 0°C ~ 1750°C 32°F ~ 3182°F
N -50°C ~ 1300°C -58°F ~ 2372°F
C -50°C ~ 1800°C -58°F ~ 3272°F
DPT -200°C ~ 850°C -328°F ~ 1562°F
LINE -1999 ~ 9999
 
Alarm Function
PV High Alarm PV Low Alarm

Related Products


IST-H Microprocessor Based Programmable lsolated Signal Transmitter

ISC 2-Channel Isolated Universal Signal Converter / Conditioner / Isolator

VT200L Separate HVAC Temperature
Humidity & CO2 Transmitter
 
 
 
 
ABOUT l PRODUCTS l SERVICE l NEWS l CONTACT