PRODUTCTS  
     
 

 

   
Home > Products > Transmitters & Converters > NST-H Microprocessor Based Programmable Signal Transmitter  
 
  NST-H Microprocessor Based Programmable Signal Transmitter  
 

 

 

Catalog

Manual

Software
  • Head mount
  • Programmable for various input signals and measuring range
  • Configurable without Power Connected
  • Inputs
  • Resistance thermometer (PT100)
  • Thermocouple (J,K,T,E,B,R,S,N,C) 
  • mV transmitter
    Output
  • 2-wire loop-power technology, 4 to 20 mA analog output
  • Fault signal on sensor break presettable
 
The  NST-H is user configurable using our software on your PC/notebook . The easy to use  software is available free from your supplier or can be downloaded from our web site and should be used in conjunction with the URC-1020 USB cable which incorporates an interface converter necessary for communications.The NST-H transmitter can be configured without any loop or power connected making it easy to configure in the workshop before installation.
 
Specification
Input Thermocouple (T/C) :
industry standard thermocouple types J, K, T, E, B, R, S, N, C (ITS-90).
Pt100 : Excitation 180uA. 2 or 3 wire connection (ITS-90 α =0.00385).
Voltage : -60mVdc to 60mVdc.
Accuracy Refer to Table 1 Input Signal
A/D Resolution 16 bits
Input Sampling Rate <200 ms
Power Supply DC 10 to 36V
Max. Load (V-10) / 0.02 ( Ω )
Output Resolution 0.6 μ A(15 bits)
Output Response Time <200 ms

Common Mode Rejection Ratio
 (CMRR)

>80 dB
Electromagnetic Compatibility En 50081-2, En 50082-2
Operating Temperature -10 to 50°C
Humidity 0 to 90% RH
 
Table 1 Input Signal
Input signal Maximum Range Accuracy
Thermocouple J -50 to 1000°C (-58 to 1832°F) ± 1°C
Thermocouple K -50 to 1370°C (-58 to 2498°F) ± 1°C
Thermocouple T -270 to 400°C (-454 to 752°F) ± 1°C
Thermocouple E               -50 to 700°C (-58 to 1292°F) ± 1°C
Thermocouple B                0 to 1750°C (32 to 3182°F)                ± 2°C (Note1)
Thermocouple R               -50 to 1750°C (-58 to 3182°F) ± 2°C
Thermocouple S               -50 to 1750°C (-58 to 3182°F) ± 2°C
Thermocouple N               -50 to 1300°C (-58 to 2372°F) ± 2°C
Thermocouple C               -50 to 1800°C (-58 to 3272°F) ± 2°C
Pt100               -200 to 600°C (-328 to 1112°F)     ± 0.2°C
mV               -60mV to 60mV         ± 0.01mV
 

Note 1: Accuracy is not guaranteed between 0 and 400°C (0 and 752°F) for type B

The standard unit is supplied set for thermocouple/PT100 inputs.
The transmitters are user configurable. 
Should you require that the factory set the inputs and ranges the full code must be specified

Loop Power Signal Transmitter
Model Type Input Output Isolated
T/C PT100 mV mA V
IST-H Head Mount V V V X X 4-20mA V
IST-D DIN Rail V V V V V 4-20mA V
IST-P Head Mount 0-60KΩ 4-20mA V
NST Head Mount V V V X X 4-20mA X
 
Dual Channel Isolated Signal Converter
Model Type Input Output 1 Output 2 Math Function Independent
Input(*Note)
T/C PT100 mV mA V
ISC-D DIN Rail V V V V V 0-24mA/0-10V 0-24mA/0-10V V X
ISC-C DIN Rail V V V V V 0-24mA/0-10V RS485 V X
ISD-D DIN Rail V V V V V 0-24mA/0-10V 0-24mA/0-10V X V
ISD-C DIN Rail V V V V V 0-24mA/0-10V RS485 X V
ISA-D DIN Rail X X V V V 0-24mA/0-10V 0-24mA/0-10V X V
ISA-C DIN Rail X X V V V 0-24mA/0-10V RS485 X V
*Note: ISD/ISA: Different input type can be set to each channel
ISC: Both channels must be set to same input type