Home > Products > Transmitters & Converters > ISC Dual Channel Isolated Signal Average Conditioner / Converter  
 
  ISC Dual Channel Isolated Signal Average Conditioner / Converter  
 

 

 

Catalog

Manual

RS-485

Software
  • Both channels must be set to same input type
  • Programmable for various input signals and measuring ranges. 
  • Configurable without Power Connected.
  • Din Rail Mount 
  • Inputs : User configurable for 
  • Resistance thermometer (PT100 / RTD)
    Thermocouple (J,K,T,E,B,R,S,N,C) 
    Also available for Voltage, Current and mV
  • The unique Math function:

  • PV1:Input 1
    PV2:Input 2
    A,B,C:Constant Factors are set by user When Average ( ÷ ) function is selected, calculation    formula is as followings


    PV1:Input 1
    PV2:Input 2
    A,B,C:Constant Factor A,B,C can be defined according to application.C≠0; ,: disable

  • Outputs : 3 models are available
    1. ISC-S : Single Analog Output : 4~20 mA、0~10VDC …
    2. ISC-D : Dual Analog Outputs : 4~20 mA、0~10VDC …
    3. ISC-C : One Analog Output (OUT1) 4~20 mA、0~10VDC … with RS485 Com port : MODBUS-RTU (OUT2)
  • High accuracy in total ambient temperature range. 
  • Sensor break fault signal level pre-setable.
 
The Din Rail converter is user configurable using our oftware on your PC/notebook . The easy to use software is available free from your supplier or can be downloaded from our web site and should be used in conjunction with the URC-1020 USB cable which incorporates an interface converter necessary for communications.The ISC converter can be configured without any loop or power connected making it easy to configure in the workshop before installation.
 
Specification
Input Thermocouple (T/C) :
industry standard thermocouple types J, K, T, E, B, R, S, N, C (ITS-90).
Pt100 : Excitation 180uA. 2 or 3 wire connection (ITS-90 α =0.00385).
Voltage : -60mVdc to 60mVdc or –10Vdc to 10Vdc.
Current : 0-24mAdc
Accuracy Refer to Table 1 Input Signal
A/D Resolution 16 bits
Input Sampling Rate <200 ms
Power Supply DC 16~32V
Power Consumption 1.7W (max)
Output Current Output : 4~20mA( Resistive load 600Ω max.)
Continuous Voltage Output : 0~10V…( Resistive load 600Ω min.)
Output Resolution 0.6 μ A(15 bits)
Output Response Time <200 ms

Common Mode Rejection Ratio
 (CMRR)

>80 dB
Electromagnetic Compatibility (EMC) En 50081-2, En 50082-2
Galvanic Isolation 2.8 KV. between input and output
Operating Temperature -10 to 50°C
Humidity 0 to 90% RH
Dimension 75mm(W)x87mm(H)x18.5mm(D)
 
Table 1 Input Signal
Input signal Maximum Range Accuracy
Thermocouple J -50 to 1000°C (-58 to 1832°F) ± 1°C
Thermocouple K -50 to 1370°C (-58 to 2498°F) ± 1°C
Thermocouple T -270 to 400°C (-454 to 752°F) ± 1°C
Thermocouple E                 -50 to 700°C (-58 to 1292°F) ± 1°C
Thermocouple B                  0 to 1750°C (32 to 3182°F)                ± 2°C (Note1)
Thermocouple R                 -50 to 1750°C (-58 to 3182°F) ± 2°C
Thermocouple S                 -50 to 1750°C (-58 to 3182°F) ± 2°C
Thermocouple N                 -50 to 1300°C (-58 to 2372°F) ± 2°C
Thermocouple C                 -50 to 1800°C (-58 to 3272°F) ± 2°C
Pt100                 -200 to 600°C (-328 to 1112°F)     ± 0.2°C
mV                 -60mV to 60mV         ± 0.01mV
Voltage (Note2)                 -10 to 10Vdc    ± 1mV
Current (Note2)                  0 to 24mAdc     ± 10μA
 

Note 1: Accuracy is not guaranteed between 0 and 400°C (0 and 752°F) for type B

Note 2: The internal DIP switch should be set

Loop Power Signal Transmitter
Model Type Input Output Isolated
T/C PT100 mV mA V
IST-H Head Mount V V V X X 4-20mA V
IST-D DIN Rail V V V V V 4-20mA V
IST-P Head Mount 0-60KΩ 4-20mA V
NST Head Mount V V V X X 4-20mA X
 
Dual Channel Isolated Signal Converter
Model Type Input Output 1 Output 2 Math Function Independent
Input(*Note)
T/C PT100 mV mA V
ISC-D DIN Rail V V V V V 0-24mA/0-10V 0-24mA/0-10V V X
ISC-C DIN Rail V V V V V 0-24mA/0-10V RS485 V X
ISD-D DIN Rail V V V V V 0-24mA/0-10V 0-24mA/0-10V X V
ISD-C DIN Rail V V V V V 0-24mA/0-10V RS485 X V
ISA-D DIN Rail X X V V V 0-24mA/0-10V 0-24mA/0-10V X V
ISA-C DIN Rail X X V V V 0-24mA/0-10V RS485 X V
*Note: ISD/ISA: Different input type can be set to each channel
ISC: Both channels must be set to same input type