- T/C, RTD, Linear Input selection.
- P, PD, ON/OFF control mode selection.
- Universal Power supply : 100-240V AC, 50/60Hz.
- 3 Alarm output. (note 1)
- Form A or Form B contact alarm function can be selected.
- 4-20mA PV Retransmission , or RS-485 communication(MODBUS RTU) is available for option.
Note1: 2nd and 3rd Alarm are available for option.
- Indicator / Controller for Temperature, Humidity, Pressure,Air-Conditioning, Gas Detector, DC Current/Voltage, ...etc.
|
Specifications |
Input |
Thermocouple : J. K. T. E. B. R. S. N.C |
RTD : DIN PT-100; JIS PT-100 |
Linear : 4~20mA; 0~50mV; 1~5V; 0~10V… |
RS-485 input |
Accuracy |
T/C±1°C; RTD±0.2°C; Linear±3μV |
Sampling Time |
0.25 sec. |
Control |
P Control : Proportional Band : 0.0~300.0% F.S |
PD Control : Proportional Band : 0.0~300.0% F.S |
Derivative Time : 0~900 sec. |
ON / OFF Control : Hysteresis 0~2000 |
Cycle Time
(0~100)
|
Relay 15 sec. |
Current Output (SSR) 1 sec. |
Continuous Current (Voltage) : 0 sec. |
Output |
Relay Contact Output : 10A / 240 VAC (Resistive load) |
Pulsed Voltage Output to Drive SSR : DC 0/24V
(Resistive 250 Ωmin.) |
Current Output : 4~20mA; (Resistive 600 Ωmax.) |
Continuous Voltage Output : 0~50mV; 1~5V; 0~10V.....
(Resistive 600 Ωmin.) |
General |
Rated Voltage : AC 100~240VAC 50 / 60Hz |
Ambient Temperature : 0~50°C |
Ambient Humidity : 0~90% |
Consumption : Less than 3VA |
|
|
Input |
Type |
TEMPERATURE RANGE ( °C ) |
TEMPERATURE RANGE ( °F ) |
J |
-50 ~ 1000°C |
-58°F ~ 1832°F |
K |
-50°C ~ 1370°C |
-58°F ~ 2498°F |
T |
-270°C ~ 400°C |
-454°F ~ 752°F |
E |
-50°C ~ 750°C |
-58°F ~ 1382°F |
B |
0°C ~ 1800°C |
32°F ~ 3272°F |
R |
0°C ~ 1750°C |
32°F ~ 3182°F |
S |
0°C ~ 1750°C |
32°F ~ 3182°F |
N |
-50°C ~ 1300°C |
-58°F ~ 2372°F |
C |
-50°C ~ 1800°C |
-58°F ~ 3272°F |
DPT |
-200°C ~ 850°C |
-328°F ~ 1562°F |
JPT |
-200°C ~ 650°C |
-328°F ~ 1202°F |
LINE |
-1999 ~ 9999 |
|
|
Alarm Function ( Form A or Form B) |
PV High Alarm |
PV Low Alarm |
Deviation High Alarm |
Deviation Low Alarm |
Band High Alarm |
Band Low Alarm |
PV High Alarm with Delay Time |
PV Low Alarm with Delay Time |
|
|
|
● Note 1: If input code ”L” is selected, please specify the input Signal and scale, for example: 4~20mA, 0.0~100.0
● Note 2: If output code ”O” is selected, please specify the output Signal, for example: 1~5V
|
|
|