| Specification |
| Sensor Measuring Range |
Temperature Range: -40~100°C |
| Relative Humidity: 0~100% |
| Measuring Resolution |
Temperature: 0.1°C |
| Relative Humidity: 0.1% |
| Measuring Accuracy |
Temperature: ±0.4°C (typ. @25°C) |
| Relative Humidity: ±3% RH (20~80%RH @25°C) |
| Response Time |
Temperature: 5~30 Sec. |
| Relative Humidity: 8 Sec. (typ.) Time for reaching 63% of a step function, valid at 25°C and 1 m/s airflow. |
| Sampling Time |
1 Sec. |
| Transmitter Operation Temperature |
-20~70°C (with LCD display) |
| -20~80°C (without LCD display) |
| Power Supply |
12~30Vdc |
| Power Comsumption |
1W Max. |
|
Current Consumption
|
<4mA |
| Output |
Analogue output: 4~20mA for 0~100% RH and 4~20mA for temperature range 0~50°C, 0~100°C or -50~50°C selectable. |
| RS-485 Communication: Modbus RTU mode Protocol with 9600/19200 Baud Rate. |
| Protection |
Electronics enclosure - IP64 |
| Sensor capsule - IP40 |
| CE Compatibility |
EN61326-1 |